Model Name |
4KTLD |
5KTLD |
6KTLD |
8KTLD |
10KTLD |
Input |
|
Max. DC input power |
6000W |
7500W |
9000W |
12000W |
15000W |
Max. DC input voltage |
|
|
550V |
|
|
Max. DC input current |
20/20A |
20/20A |
20/20A |
20/26A |
20/30A |
MPPT voltage range |
80-550V |
Recommended MPPT operating voltage |
360V |
Starting voltage |
50V |
No.Of MPPT |
2 |
Max. no.of strings per MPPT |
1/1 |
1/2 |
Output |
|
Rated output power |
4000W |
5000W |
6000W |
8000W |
10000W |
Max. output power |
4.4kVA |
5.5kVA |
6.6kVA |
8.8kVA |
11kVA |
Max. output current |
20A |
25A |
27.3A |
36.4A |
45.5A |
Rated grid voltage |
230V |
Grid voltage range |
160~270Vac (adjustable) |
Rated grid frequency |
50Hz/60Hz |
Grid frequency range |
45~55Hz/55~65Hz |
THD |
<2% (Under the rated power) |
Power factor |
0.99 (Under the rated power) / Adjustable range: 0.8 leading-0.8 lagging |
DC current injection |
<0.5% (Under the rated power) |
System data |
|
Max. efficiency |
98.10% |
98.10% |
98.10% |
98.10% |
98.10% |
Euro. efficiency |
97.50% |
97.50% |
97.50% |
97.50% |
97.60% |
Humidity range |
0-100% non-condensing |
Cooling type |
Natural cooling |
Intelligent forced air cooling |
Temperature range |
-25~+60°C |
Power consumption at night |
<1W |
Max. working altitude |
4000m |
Display |
LED(optional: LCD) |
Communication interface |
WIFI(optional: RS485 or GPRS) |
Protection |
|
DC reverse-polarity protection |
Yes |
Short circuit protection |
Yes |
Output over current protection |
Yes |
Output over voltage protection |
Yes |
Insulation resistance monitoring |
Yes |
Residual current detection |
Yes |
Surge protection |
Yes |
Grid monitoring |
Yes |
Islanding protection |
Yes |
Temperature protection |
Yes |
Integrated DC switch |
Yes |
Mechanical data |
|
Dimensions (WHD) |
347*368*167mm |
347*368*190mm |
Weight |
10kg |
11kg |
Protection class |
IP66 |
Standard |
|
Safety standard/EMC standard |
NB/T32004-2018, IEC62109, IEC61000, IS16169 & IS16221(BIS) |
Grid-connected standard |
IEC61727, EN50549-1, VDE-4105, NRS-097-2-1, OVE-Richtlinie R25, UNE217001/2, Ordinance No.140 |
Other standard |
IEC61683, IEC62116, EN50530, IEC60068 |