Model Name |
6KTLC |
8KTLC |
10KTLC |
12KTLC |
15KTLC |
17KTLC |
Input |
|
Max. DC input power |
9000W |
12000W |
15000W |
18000W |
22500W |
25500W |
Max. DC input voltage |
1100V |
Max. DC input current |
20/20A |
20/30A |
MPPT voltage range |
180-1000V |
Recommended MPPT operating voltage |
650V |
Starting voltage |
180V |
No.Of MPPT |
2 |
2 |
Max. no.of strings per MPPT |
1/1 |
1/2 |
Output |
|
Rated output power |
6000W |
8000W |
10000W |
12000W |
15000W |
17000W |
Max. output power |
6.6kVA |
8.8 kVA |
11kVA |
13.2kVA |
16.5kVA |
18.7kVA |
Max. output current |
10A |
13.3A |
16.7A |
20A |
24A |
28.3A |
Rated grid voltage |
400V |
Grid voltage range |
310~480Vac |
Rated grid frequency |
50Hz/60Hz |
Grid frequency range |
45~55Hz/55~65Hz |
THD |
<2% (Under the rated power) |
Power factor |
0.99 (Under the rated power) / Adjustable range: 0.8 leading~0.8 lagging |
DC current injection |
<0.5% (Under the rated power) |
System data |
|
Max. efficiency |
98.50% |
98.50% |
98.60% |
98.70% |
98.70% |
98.70% |
Euro. efficiency |
98% |
98% |
98.20% |
98.10% |
98.20% |
98.20% |
Humidity range |
0~100%, non-condensing |
Cooling type |
Intelligent forced air cooling |
Temperature range |
-25~+60°C |
Power consumption at night |
<1W |
Max. working altitude |
4000m |
Display |
LED(optional: LCD) |
Communication interface |
WIFI(optional: RS485 or GPRS) |
Protection |
|
DC reverse-polarity protection |
Yes |
Short circuit protection |
Yes |
Output over current protection |
Yes |
Output over voltage protection |
Yes |
Insulation resistance monitoring |
Yes |
Residual current detection |
Yes |
Surge protection |
Yes |
Grid monitoring |
Yes |
Islanding protection |
Yes |
Temperature protection |
Yes |
Integrated DC switch |
Yes |
Mechanical data |
|
Dimensions (WHD) |
427*450*204mm |
Weight |
15kg |
Protection class |
IP66 |
Standard |
|
Safety standard/EMC standard |
NB/T32004-2018, IEC62109, IEC61000, IS16169 & IS16221(BIS) |
Grid-connected standard |
IEC61727, EN50549-1, VDE-4105, NRS-097-2-1, OVE-Richtlinie R25, UNE217001/2, Ordinance No.140 |
Other standard |
IEC61683, IEC62116, EN50530, IEC60068 |